SES-ASA Series 2400

PLC SYSTEM WITH DISTRIBUTED INTELLIGENCE

Category:

Description

DESCRIPTION

In the last years many DCS manufacturers were specifying DCS System for safety application.However today the new IEC-61508 standard clearly sepaterates the application of DCS form safety systems. Process Control Systems are not suitable for Plant Safety Protection because they react to changes in the process and not to hazard events. The complexity of processes and the size of plants of today may allow minor problems to escalate quickly into critical conditions. Our ENHANCED DEDICATED PLC FG-ESD 2400 SYSTEM is designed to provide a faster and reliable protection to your investment and personnel. The FG-ESD 2400 employs a unique advanced concept of Fire & Gas protection with customized Fire & Gas cards with Master & Slave CPU with hot-swap capability firmware program. The FG-ESD 2400 can be easily interfaced with DCS/SCADA, Host Computer or other existing system via RS232-RS485 or MODBUS™.

SYSTEM FEATURES

  • Over 4000 Digital / Analog and Addressable Devices
  • Single or Dual CPU capability
  • Field Gas & Flame Detection Cards with FAIL-TOSAFE firmware program
  • Dual serial buses to interfaces I/O cards with external digital control panels
  • Single or redundant I/O cards configuration
  • CPUs’ hot-replacement and I/O cards
  • Multitasking operating system with built-in diagnostic
  • Optoisolated signals to/from field
  • MODBUSTM RTU communication
  • Field expandable open architecture
  • Fully configurable, programming & testing using PC support
  • Self-reporting
Model Name MCM-100
System Specification
Processor Intel Atom® x7-E3950 processor
Video 1x DisplayPort
Memory DDR3L 1066 SODIMM 2 GB
Storage Factory installed 128 GB mSATA SSD
Ethernet 2x GbE LAN (Intel® I210-IT)
Serial Port 2x COM (2 x RS-232/422/485)
USB 2x USB 2.0 + 2x USB 3.0
Mini PCIe 2x Mini PCIe card slots
Wireless Kit (option) Wi-Fi/4G LTE wireless Kit
Power Supply 6 ~ 36 VDC, Optional 40W AC/DC adapter
Vibration Measurement I/O Specification
Channels 4CH
Resolution 24-Bit
Max. Sampling Rate 128 kS/s
Input Range ±10V
Input Mode Diff/P-Diff
Input Coupling AC/DC
IEPE Excitation Current 0 or 2mA (IEPE compliance: 24V)
Over-Voltage Protection ±60V
DC accuracy – Offset Error Typical: ±0.15mV, Max. ±0.3mV
DC accuracy – Gain Error Typical: ±0.15%, Max. ±0.3%
System Noise 50 μVrms
-3dB Bandwidth 0.49 * sampling rate
AC Cutoff 0.4Hz (-3dB), 2.4Hz (-0.1dB)
Flatness ±0.01 dB (20 Hz to 1 kHz)
CMRR 60 dB (20 Hz to 1 kHz)
Crosstalk -100 dB
Dynamic Range 100 dB
SFDR 104 dB
THD -94 dB
THD+N -91 dB
Trigger Source Analog or digital, software selectable
Trigger Mode Post, delay, middle, pre-trigger, re-trigger
Auto-Calibration Yes
DIO 2 programmable function I/O
Mechanical
Dimensions 183 (W) x 110 (D) x 83.85 (H) mm
Construction Full Aluminum Alloy
Mounting DIN-rail/wall mountable
Environmental
Operating Temperature 0 to 55°C (32 to 131˚F)
Storage Temperature -20 to 70°C (-4 to 158˚F)
Humidity approx. 95% @ 40°C (non-condensing)
Vibration Operating 5 Grms, 5-500 Hz, 3 axes w/ mSATA SSD
ESD Contact +/-4 KV, Air +/-8 KV
Shock Operating 100 G, half sine 11 ms duration w/ mSATA SSD
EMC CE & FCC Class B (EN61000-6-4/EN61000-6-2)