قابل سفارش
موجود در انبار
Vibration inputs filtering | Filtered for protection against electromagnetic interference |
Vibration outputs filtering | Filtered for protection against electromagnetic interference |
Speed / phase reference inputs filtering | Filtered for protection against electromagnetic interference |
DSI control signal inputs operating principle | Detection of an open or closed circuit on the input |
Alarm reset (AR) | A closed contact between the AR and RET inputs resets latched alarms |
Danger bypass (DB) | A closed contact between the DB and RET inputs allows the operator to inhibit the danger relay outputs |
Trip multiply (TM) | A closed contact between the TM and RET inputs |
Quantity and type alarm outputs | 32 outputs on rack backplane bus, for use by the VM600 relay cards |
DC outputs | 4 per IOC4T card |
Signal range | 0 to 10 V or 4 to 20 mA |
Accuracy | ≤ ±0.5% |
Linearity error | ≤ ±0.5% |
Admissible load on output | > 100 kΩ for voltage output < 325 Ω for current output |
Contact arrangement | 1 x NC or 1 x NO contact/relay (user selectable). The selected contacts are available on J2. |
Nominal rated voltage | 250 VAC |
Nominal rated current | 5 AAC |
Maximum breaking capacity | 1250 VA |